Quick and Easy Steps for Troubleshooting a VFD
Modern Variable Frequency Drives are complex. By the mid 80's, almost all VFDs had adopted microprocessors as their primary design architecture. By the early 90's, Vector Drive technology was commonplace, and AC Drives began to appear in torque sensitive applications previously thought to be the exclusive domain of DC Drives.
Modern drives are remarkably reliable, and with almost all adjustments being digital, they rarely need tuning once started and commissioned properly. In the early days of EMA, it was commonplace for field service engineers to carry a supply of transistors, resistors, and integrated circuits along with a soldering iron on most service calls. Many long nights and days were spent troubleshooting down to a discrete component level, and even changing circuit gains to stabilize a drive by swapping resistors in and out of an operational amplifier circuit. Thankfully, for the most part, those days are over.
Here are a few simple tips that should prove helpful for troubleshooting most VFDs.
1. Check the input bridge.
This is done (with power removed), and after waiting a bit until there is no voltage on the DC bus. Switch your digital VOM to Diode Check mode. Place the negative VOM lead on the positive DC bus. This is often labeled as "+" on or near the power terminals. Then place the positive VOM lead on each of the incoming three phases. You should read a forward diode drop (.3 to .6 volts) on each leg. If this checks out, then place the positive VOM lead on the negative bus. This is usually labeled "-" on or near the power terminals. Then place the negative VOM lead on all three incoming phases and again, look for a forward diode drop. If you read a short, then the input bridge is shorted, if an open, then likely the charge resistor is open.
2. Check the output devices.
Keeping the positive VOM lead on the negative bus "-", place the negative VOM lead on each of the three motor output terminals. You should read again, a forward diode drop. Place the negative VOM lead on the positive bus "+", and the positive VOM lead on each of the motor output terminals. Look for a forward diode drop. If you read a short, then the output device is shorted. If you read an open, then either the output device is damaged, or the DC Bus fuse is open.
Physically inspect the output devices. They can fail in a manner where they can be physically exploded, but you'll still read the diode drop.

3. Check the bus capacitors.
Physically inspect the capacitors for signs of damage. This can include a cracked or deformed casing, or the pressure plug popped out of the top. Then measure from the positive to negative DC bus with your VOM set to OHMS.
You should not see a short.
If your
drive has several caps, it is possible that one could be open. The only
way to be certain of this is to put an oscilloscope on the bus and look
for ripple. Caution, this is a power on check, and should only
be done by technicians familiar with doing such tests on a high energy
circuit.

4. Check the internal power supplies
Assuming,
that all of your power off checks pass, then apply power to the drive.
In most VFDs, the power supplies are obtained from the DC bus via one
or more switching power supplies. A quick check of this is if the
keypad lights up. If it does not, then your switching power supply is
dead. (assuming that your bus charge light indicates bus voltage).

5. Check the programs.
Many of EMA's service calls on reportedly faulty drives turn out to be programming errors. It is possible, although it should be used as a last resort, to reset all programming to factory defaults. This is done differently by different manufacturers, and is usually detailed in the VFD manual. This puts the VFD back to the default programming that it came with when new.
A very common error:
The drive will be programmed to get its reference or its stop and start from the keypad instead of remotely. Many drives now have indications on the keypad if the drive is set for Remote or Local operation. (Local is keypad control).